KIT BOXPDS SMART II

KIT BOXPDS SMART II

Evacuation route pressurisation systems with advanced control, standby fan and test certificate according to the European standard EN 12101-6:2022

System with test certification according to the requirements of the European standard EN 12101-6:2022, and additional tests for electromagnetic compatibility, environmental resistance and IP protection degree.

The KIT BOXPDS SMART II automatically regulates the airflow and is able to maintain the 50 Pa of overpressure even in the presence of leaks in the installation. The system is able to maintain the overpressure (Pressure criteria) and reach the 90% of the required flow rate within 3 seconds after opening or closing a door (Airflow criteria).

Utility model: ES 1 226 660 U.

KIT BOXPDS SMART II
• Device with advanced control, consisting of a BOXPDS SMART control panel, an external control panel, 2 CJHCH ventilation units and a DAMPER BOX SMART with integrated optical smoke detector.

BOXPDS SMART
• Variable frequency drive.
• High precision differential pressure probe.
• Electrical panel with magneto thermal protections and general power supply failure indication.
• Electronic control for alarm management, maintenance, ModBUS RTU and TCP port for connection to BMS (Building Management Systems) and control by DAMPER BOX SMART.
• Certified power supply with batteries to ensure power supply to control equipment in the event of a power failure.
• Quick set up for intuitive configuration.
• Possibility of controlling 3 motorised air intakes of the DAMPER BOX SMART, HATCH or WALL type.
• Smoke detector with automatic reset.
• Pressurisation or despressurisation/extraction mode.
• Possibility of connecting several pressure sensors for large stairwells and choosing the control mode: Maximum, minimum or average.
• External sensors connection: Humidity, temperature and wind.
• Includes time programming to activate daily ventilation.

Control panel:
• External control panel with touch screen for real time pressure display, system configuration and calibration, status lights and manual system activation.
• Possibility of connecting up to 3 KIT BOXPDS SMART.
• Auto-Manual-Off selector.
• Fire alarm reset selector.
• Test selector.

On request:
• Automatic switching system for backup fan.